Skip to main content

Amanah Tech

Talk to an Expert:   +1 416-603-9825 x 1

🏆 Price Match Guarantee  We’ll beat any colocation quote by 10%  ·  151 Front Street West, Toronto

In this article

INSIDE 151 FRONT SERIES

Coming soon

Colocate at 151 Front Street West.

TOR1 is sold out but TOR2 has availability. Talk to the team about rack space.

Deep lake water cooling, explained by a data centre operator

Toronto's deep lake water cooling draws cold water from 83 metres down in Lake Ontario. See how it cools a data centre suite, from lake intake to rack.

In this article

Chilled-water pipe with condensation on bare steel above a bolted flange, in front of a server rack in a dark data centre suite

Deep lake water cooling is Toronto’s district cooling system. Enwave draws water from 83 metres down in Lake Ontario, cold enough to chill buildings all year, and uses it to cool more than 100 downtown buildings. 151 Front Street West is one of them. In Amanah’s suites, that lake-chilled supply sits under air cooling and aisle containment, so a July heat wave does not change how we cool your rack.

Key takeaways
  • Enwave draws water through intake pipes about 5 km offshore, from 83 metres down, where the lake stays cold year round.
  • Lake water never touches a server. Heat exchangers pass its cold to separate water loops, which feed the cooling units in the suite.
  • Enwave puts the energy saving at about 90%. Cooling could account for 38% to 40% of a data centre’s electricity, according to the US Congressional Research Service.
  • The system circulates water through closed loops at the building instead of evaporating it, which is how cooling towers lose water.
  • Inside the suite, air cooling and containment do the rest. TOR2 adds N+1 in-row cooling with hot and cold aisle containment for denser racks.

What is deep lake water cooling?

Deep lake water cooling is a district cooling system run by Enwave, one of our technology partners. It replaces most of the work a building’s own chillers would do, using cold water from the bottom of Lake Ontario. Water is densest at about 4 °C, so the coldest water sinks and the deep layer of the lake stays cold through summer and winter.

Three intake pipes run about 5 km offshore and draw from 83 metres down. Enwave completed the system in 2004, and it now serves more than 100 downtown buildings, including City Hall and Toronto General Hospital. Enwave estimates it saves the city about 90,000 MWh of electricity a year.

Lake Ontario on a bright summer afternoon, with the downtown Toronto skyline in heat haze across the water

Engineers call this free cooling because nature supplies the cold. Pumping, heat exchange and the distribution network still cost money and energy, so the word refers only to where the cold comes from.


How does lake water cool a data centre at 151 Front Street West?

The cold passes through separate water loops before it reaches the air in a suite. Lake water gives up its cold through heat exchangers to Enwave’s loop, which chills the building’s own water loop, which feeds the cooling units inside each suite. Each handoff happens across a heat exchanger between separate loops, so no water mixes.

Diagram of deep lake water cooling at 151 Front Street West: Lake Ontario intake, Enwave heat exchangers, building water loop, cooling units, aisle containment and the rack, with separate loops at every handoff

Inside the suite, three layers do the work:

  1. The supply. Lake-chilled water from Enwave arrives at a steady temperature, whatever the weather outside.
  2. The cooling units. In TOR2, in-row cooling units sit between the racks, so they make cold air within a metre or two of the servers that need it. TOR2’s cooling is N+1 redundant. TOR1 pairs the lake supply with N+1 mechanical cooling.
  3. The containment. Hot and cold aisle containment in TOR2, and hot aisle containment in TOR1, keep exhaust air from mixing with supply air. Without containment, the cooling units spend much of their cold on the room instead of the equipment.

“Lake water gives us a cold, steady supply to work from. Everything we build inside the suite, from in-row units to containment, starts from that baseline.” – Amanah operations team

For you as a customer, the supply temperature stays put. The variables our team manages sit inside the suite: airflow, containment and the heat each rack produces.


Why does a data centre need so much cooling?

Almost every watt a server draws turns into heat, and that heat has to leave the room as fast as the servers make it. A rack drawing 10 kW works, for practical purposes, as a 10 kW heater running all day. Data centre cooling, whether from rooftop towers or lake water, is the work of carrying that heat out of the building.

Cooling is one of the largest lines on a data centre’s power bill. A 2025 Congressional Research Service report, citing Deloitte, says cooling systems could account for 38% to 40% of a data centre’s electricity. Demand keeps climbing: the International Energy Agency projects global data centre electricity demand will more than double by 2030, to around 945 TWh.

Cooling is also an uptime risk. When heat removal falls behind, servers throttle and then shut down. In both Amanah suites cooling runs N+1, as does facility power, so the remaining units can carry the load when one fails.


How do data centres use water, and does lake cooling use it up?

Most data centres that use water lose it to evaporation. Deep lake water cooling circulates water through closed loops at the building and sends it back, instead of evaporating it on the roof.

The difference is between water consumed and water circulated. A cooling tower sprays water over surfaces so it evaporates and carries heat away, and the operator has to replace that water constantly. Towers also run blowdown, flushing out the scale that evaporation leaves behind, which consumes more water.

Rooftop evaporative cooling tower venting a plume of water vapour into an overcast sky

Toronto’s lake water takes a different path. The city draws it for the drinking water supply and treats it at the Island Filtration Plant. Enwave borrows its cold through heat exchangers on the way, and the water continues into the city’s supply slightly warmer. Enwave’s own loop returns to the pumping station to repeat the cycle. Enwave estimates the system saves about 220 million gallons of water a year compared with conventional cooling.

Lake cooling still pumps large volumes of water through the city’s system. Its saving is the water that cooling towers would otherwise evaporate.


How does lake cooling compare with other data centre cooling systems?

Lake cooling replaces the most energy-hungry part of a conventional cooling chain: the chiller plant that makes cold water from scratch. The rest of the chain, the units and the containment in the suite, still needs careful design.

MethodEnergy use (relative)Water useClimate dependenceBest fit
Water-cooled chillers with cooling towersHigh: chillers make the cold, towers reject the heatHigh: tower water evaporates and must be replacedLess effective in hot, humid weatherLarge sites with a reliable water supply
Air-side economizersLow when outside air is coolLowHigh: relies on cool, clean outside airCool, dry climates
Air-cooled chillersHighest in hot weatherLowWorks anywhere, costs more in heatSites with no natural cold source or water supply
Liquid at the chip (direct-to-chip, immersion)Lower fan energy at the rackDepends on the facility loop behind itLowVery high-density AI and HPC racks
Deep lake supplyAbout 90% less than conventional cooling, per EnwaveNo evaporation at the buildingLow: the deep intake stays cold year roundBuildings on a district network fed by deep, cold water

Only the deep lake row carries a measured figure. The other energy ratings are relative, for orientation.

Air-side economizers are the other common form of free cooling. They pull in outside air when it is cold enough, which works well in a Toronto winter and poorly in a humid August. Lake cooling avoids that seasonality because the intake sits far below the reach of summer heat.

Liquid systems win for the densest AI racks, because they remove heat at the chip rather than from the air. Air cooling on a lake-chilled supply suits air-cooled servers and GPU nodes built for front-to-back airflow, and we tell buyers plainly when a workload needs liquid.


What does lake cooling mean for a high-density rack?

A stable cold supply lets you size a suite’s cooling for its racks rather than for the weather. The supply temperature does not swing with the seasons, so the cooling units never have to be sized for the worst week of the year. That leaves airflow and containment as the variables that decide how dense a rack can run.

Doubling a rack’s power draw doubles the heat it pushes into the aisle, and any mixing of exhaust with supply air shows up first at the densest racks. TOR2, opened in 2025 on the sixth floor, places N+1 in-row cooling between the racks and closes both the hot and cold aisles for that reason. If you are planning racks above what a standard suite supports, start with high-density colocation in TOR2.

Contained cold aisle in a data centre, with black server cabinets on both sides, perforated floor tiles, clear roof panels and a sliding door at the end

A building-wide density figure tells you little about your own racks. The number to ask for is the per-rack figure in the suite you would occupy, checked against your hardware’s actual power draw.


What should you ask a provider about cooling?

Ask where the cold comes from, what one failure takes away, and what the provider can support for your rack. These five questions expose a weak cooling design quickly:

  1. Where does the chilled water come from, and what happens if that source is interrupted?
  2. What is the redundancy level for cooling, and can a unit be serviced without a shutdown?
  3. What containment is in place: hot aisle, cold aisle, both or none?
  4. What is the maximum density per rack in the suite I would occupy, not the building average?
  5. What changes in a heat wave, and what changes during planned maintenance?

Bring the list on a tour and ask to see the containment for yourself. Our guide to choosing a data centre at 151 Front applies the same approach to network and security. For the power side, see how power redundancy works.


How Amanah fits

Amanah runs two suites at 151 Front Street West, both cooled with Enwave deep lake water and air-cooled inside the suite. TOR1, on the third floor since 2005, pairs the Enwave lake supply with N+1 mechanical cooling and hot aisle containment. TOR2, opened in 2025 on the sixth floor, uses N+1 in-row cooling and hot and cold aisle containment.

The facility is “built to the Tier III standard across power and cooling, with concurrent maintainability on both.” Power is N+1 redundant. Our own team runs the suites, so the people who answer your cooling questions also maintain the equipment. See Amanah’s Toronto data centres for both suites side by side.

We do not offer liquid cooling at the rack. If your workload needs direct-to-chip or immersion, we will say so on the first call.

Book a tour

See lake-cooled suites in person.

Walk TOR1 and TOR2 at 151 Front, look at the containment and bring your density questions.

Book a tour

Questions about this topic

Does lake water touch the servers?

No. Lake water stays in its own pipes and gives up its cold through heat exchangers. The cold passes to Enwave’s loop, then to the building’s loop, which feeds the cooling units in the suite. Those units chill the air that cools the servers, and lake water never enters the data hall or mixes with another loop.

What happens to the lake water after it is used?

The city draws the lake water for Toronto’s drinking water supply and treats it at the Island Filtration Plant. Enwave takes its cold through heat exchangers along the way, and the water carries on into the city’s supply slightly warmer. Enwave’s own cooling loop returns to the pumping station and repeats the cycle, circulating the water rather than evaporating it.

Does deep lake water cooling work in summer?

Yes. Water is densest at about 4 °C, so the coldest water sinks to the bottom of Lake Ontario and stays there through July and August. Summer heat raises the load on the cooling units inside a suite, but the water at the 83-metre intake stays cold.

Why do data centres need water?

Many data centres cool with evaporative cooling towers, which use water to carry heat away. That water evaporates and has to be replaced, and tower blowdown consumes more. Deep lake water cooling uses water differently: it moves cold through closed loops at the building and sends the water back instead of evaporating it.

Can lake-cooled suites handle AI hardware?

It depends on the rack’s power draw and whether the hardware can run on air cooling. Amanah’s suites are air-cooled on a lake-chilled supply, and TOR2 adds N+1 in-row cooling with hot and cold aisle containment for denser racks. Amanah does not offer liquid cooling at the rack, so hardware that needs direct-to-chip or immersion is better placed with a provider that does. Bring your per-rack power figures and we will tell you on the first call.

Tags